Module: QuickServiceRestaurant
- Defined in:
- lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb
Overview
Custom changes for the QuickServiceRestaurant prototype. These are changes that are inconsistent with other prototype building types.
Instance Method Summary collapse
- #add_door_infiltration(climate_zone, model) ⇒ Object
-
#add_extra_equip_kitchen(model) ⇒ Object
add extra equipment for kitchen.
- #add_zone_mixing(model) ⇒ Object
- #adjust_clg_setpoint(climate_zone, model) ⇒ Object
- #model_custom_hvac_tweaks(building_type, climate_zone, prototype_input, model) ⇒ Object
- #model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) ⇒ Object
- #model_update_exhaust_fan_efficiency(model) ⇒ Object
-
#reset_kitchen_oa(model) ⇒ Object
In order to provide sufficient OSA to replace exhaust flow through kitchen hoods (3,300 cfm), modeled OSA to kitchen is different from OSA determined based on ASHRAE 62.1.
- #update_sizing_zone(model) ⇒ Object
- #update_waterheater_loss_coefficient(model) ⇒ Object
Instance Method Details
#add_door_infiltration(climate_zone, model) ⇒ Object
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 27 def add_door_infiltration(climate_zone, model) # add extra infiltration for dining room door and attic (there is no attic in 'DOE Ref Pre-1980') unless template == 'DOE Ref 1980-2004' || template == 'DOE Ref Pre-1980' dining_space = model.getSpaceByName('Dining').get attic_space = model.getSpaceByName('Attic').get infiltration_diningdoor = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration_attic = OpenStudio::Model::SpaceInfiltrationDesignFlowRate.new(model) infiltration_diningdoor.setName('Dining door Infiltration') infiltration_per_zone_diningdoor = 0 infiltration_per_zone_attic = 0.0729 if template == '90.1-2004' infiltration_per_zone_diningdoor = 0.902834611 infiltration_diningdoor.setSchedule(model_add_schedule(model, 'RestaurantFastFood DOOR_INFIL_SCH')) elsif template == '90.1-2007' case climate_zone when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3A', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C', 'ASHRAE 169-2006-4A', 'ASHRAE 169-2006-4B', 'ASHRAE 169-2006-4C' infiltration_per_zone_diningdoor = 0.902834611 infiltration_diningdoor.setSchedule(model_add_schedule(model, 'RestaurantFastFood DOOR_INFIL_SCH')) else infiltration_per_zone_diningdoor = 0.583798439 infiltration_diningdoor.setSchedule(model_add_schedule(model, 'RestaurantFastFood VESTIBULE_DOOR_INFIL_SCH')) end elsif template == '90.1-2010' || template == '90.1-2013' case climate_zone when 'ASHRAE 169-2006-1A', 'ASHRAE 169-2006-2A', 'ASHRAE 169-2006-2B', 'ASHRAE 169-2006-3A', 'ASHRAE 169-2006-3B', 'ASHRAE 169-2006-3C' infiltration_per_zone_diningdoor = 0.902834611 infiltration_diningdoor.setSchedule(model_add_schedule(model, 'RestaurantFastFood DOOR_INFIL_SCH')) else infiltration_per_zone_diningdoor = 0.583798439 infiltration_diningdoor.setSchedule(model_add_schedule(model, 'RestaurantFastFood VESTIBULE_DOOR_INFIL_SCH')) end end infiltration_diningdoor.setDesignFlowRate(infiltration_per_zone_diningdoor) infiltration_diningdoor.setSpace(dining_space) infiltration_attic.setDesignFlowRate(infiltration_per_zone_attic) infiltration_attic.setSchedule(model_add_schedule(model, 'Always On')) infiltration_attic.setSpace(attic_space) end end |
#add_extra_equip_kitchen(model) ⇒ Object
add extra equipment for kitchen
69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 69 def add_extra_equip_kitchen(model) kitchen_space = model.getSpaceByName('Kitchen') kitchen_space = kitchen_space.get kitchen_space_type = kitchen_space.spaceType.get elec_equip_def1 = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def2 = OpenStudio::Model::ElectricEquipmentDefinition.new(model) elec_equip_def1.setName('Kitchen Electric Equipment Definition1') elec_equip_def2.setName('Kitchen Electric Equipment Definition2') case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013' elec_equip_def1.setFractionLatent(0) elec_equip_def1.setFractionRadiant(0.25) elec_equip_def1.setFractionLost(0) elec_equip_def2.setFractionLatent(0) elec_equip_def2.setFractionRadiant(0.25) elec_equip_def2.setFractionLost(0) if template == '90.1-2013' elec_equip_def1.setDesignLevel(457.5) elec_equip_def2.setDesignLevel(570) else elec_equip_def1.setDesignLevel(515.917) elec_equip_def2.setDesignLevel(851.67) end # Create the electric equipment instance and hook it up to the space type elec_equip1 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def1) elec_equip2 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def2) elec_equip1.setName('Kitchen_Reach-in-Freezer') elec_equip2.setName('Kitchen_Reach-in-Refrigerator') elec_equip1.setSpaceType(kitchen_space_type) elec_equip2.setSpaceType(kitchen_space_type) elec_equip1.setSchedule(model_add_schedule(model, 'RestaurantFastFood ALWAYS_ON')) elec_equip2.setSchedule(model_add_schedule(model, 'RestaurantFastFood ALWAYS_ON')) when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' elec_equip_def1.setDesignLevel(577) elec_equip_def1.setFractionLatent(0) elec_equip_def1.setFractionRadiant(0) elec_equip_def1.setFractionLost(1) # Create the electric equipment instance and hook it up to the space type elec_equip1 = OpenStudio::Model::ElectricEquipment.new(elec_equip_def1) elec_equip1.setName('Kitchen_ExhFan_Equip') elec_equip1.setSpaceType(kitchen_space_type) elec_equip1.setSchedule(model_add_schedule(model, 'RestaurantFastFood Kitchen_Exhaust_SCH')) end end |
#add_zone_mixing(model) ⇒ Object
186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 186 def add_zone_mixing(model) # add zone_mixing between kitchen and dining space_kitchen = model.getSpaceByName('Kitchen').get zone_kitchen = space_kitchen.thermalZone.get space_dining = model.getSpaceByName('Dining').get zone_dining = space_dining.thermalZone.get zone_mixing_kitchen = OpenStudio::Model::ZoneMixing.new(zone_kitchen) zone_mixing_kitchen.setSchedule(model_add_schedule(model, 'RestaurantFastFood Hours_of_operation')) case template when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' zone_mixing_kitchen.setDesignFlowRate(0.834532374) when '90.1-2007', '90.1-2010', '90.1-2013' zone_mixing_kitchen.setDesignFlowRate(0.416067345) when '90.1-2004' zone_mixing_kitchen.setDesignFlowRate(0.826232888) end zone_mixing_kitchen.setSourceZone(zone_dining) zone_mixing_kitchen.setDeltaTemperature(0) end |
#adjust_clg_setpoint(climate_zone, model) ⇒ Object
133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 133 def adjust_clg_setpoint(climate_zone, model) ['Dining', 'Kitchen'].each do |space_name| space_type_name = model.getSpaceByName(space_name).get.spaceType.get.name.get thermostat_name = space_type_name + ' Thermostat' thermostat = model.getThermostatSetpointDualSetpointByName(thermostat_name).get case template when '90.1-2004', '90.1-2007', '90.1-2010' if climate_zone == 'ASHRAE 169-2006-2B' || climate_zone == 'ASHRAE 169-2006-1B' || climate_zone == 'ASHRAE 169-2006-3B' case space_name when 'Dining' thermostat.setCoolingSetpointTemperatureSchedule(model_add_schedule(model, 'RestaurantFastFood CLGSETP_SCH_NO_OPTIMUM')) when 'Kitchen' thermostat.setCoolingSetpointTemperatureSchedule(model_add_schedule(model, 'RestaurantFastFood CLGSETP_KITCHEN_SCH_NO_OPTIMUM')) end end end end end |
#model_custom_hvac_tweaks(building_type, climate_zone, prototype_input, model) ⇒ Object
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 6 def model_custom_hvac_tweaks(building_type, climate_zone, prototype_input, model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Started building type specific adjustments') # add extra equipment for kitchen add_extra_equip_kitchen(model) # add extra infiltration for dining room door and attic add_door_infiltration(climate_zone, model) # add zone_mixing between kitchen and dining add_zone_mixing(model) # Update Sizing Zone update_sizing_zone(model) # adjust the cooling setpoint adjust_clg_setpoint(climate_zone, model) # reset the design OA of kitchen reset_kitchen_oa(model) OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Model', 'Finished building type specific adjustments') return true end |
#model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) ⇒ Object
216 217 218 219 220 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 216 def model_custom_swh_tweaks(model, building_type, climate_zone, prototype_input) update_waterheater_loss_coefficient(model) return true end |
#model_update_exhaust_fan_efficiency(model) ⇒ Object
168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 168 def model_update_exhaust_fan_efficiency(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013' model.getFanZoneExhausts.sort.each do |exhaust_fan| fan_name = exhaust_fan.name.to_s if fan_name.include? 'Dining' exhaust_fan.setFanEfficiency(1) exhaust_fan.setPressureRise(0) end end when 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' model.getFanZoneExhausts.sort.each do |exhaust_fan| exhaust_fan.setFanEfficiency(1) exhaust_fan.setPressureRise(0.000001) end end end |
#reset_kitchen_oa(model) ⇒ Object
In order to provide sufficient OSA to replace exhaust flow through kitchen hoods (3,300 cfm), modeled OSA to kitchen is different from OSA determined based on ASHRAE 62.1. It takes into account the available OSA in dining as transfer air.
155 156 157 158 159 160 161 162 163 164 165 166 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 155 def reset_kitchen_oa(model) space_kitchen = model.getSpaceByName('Kitchen').get ventilation = space_kitchen.designSpecificationOutdoorAir.get ventilation.setOutdoorAirFlowperPerson(0) ventilation.setOutdoorAirFlowperFloorArea(0) case template when '90.1-2007', '90.1-2010', '90.1-2013' ventilation.setOutdoorAirFlowRate(1.14135966) when '90.1-2004', 'DOE Ref Pre-1980', 'DOE Ref 1980-2004' ventilation.setOutdoorAirFlowRate(0.7312) end end |
#update_sizing_zone(model) ⇒ Object
114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 114 def update_sizing_zone(model) case template when '90.1-2007', '90.1-2010', '90.1-2013' zone_sizing = model.getSpaceByName('Dining').get.thermalZone.get.sizingZone zone_sizing.setCoolingDesignAirFlowMethod('DesignDayWithLimit') zone_sizing.setCoolingMinimumAirFlowperZoneFloorArea(0.003581176) zone_sizing = model.getSpaceByName('Kitchen').get.thermalZone.get.sizingZone zone_sizing.setCoolingDesignAirFlowMethod('DesignDayWithLimit') zone_sizing.setCoolingMinimumAirFlowperZoneFloorArea(0) when '90.1-2004' zone_sizing = model.getSpaceByName('Dining').get.thermalZone.get.sizingZone zone_sizing.setCoolingDesignAirFlowMethod('DesignDayWithLimit') zone_sizing.setCoolingMinimumAirFlowperZoneFloorArea(0.007111554) zone_sizing = model.getSpaceByName('Kitchen').get.thermalZone.get.sizingZone zone_sizing.setCoolingDesignAirFlowMethod('DesignDayWithLimit') zone_sizing.setCoolingMinimumAirFlowperZoneFloorArea(0) end end |
#update_waterheater_loss_coefficient(model) ⇒ Object
206 207 208 209 210 211 212 213 214 |
# File 'lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb', line 206 def update_waterheater_loss_coefficient(model) case template when '90.1-2004', '90.1-2007', '90.1-2010', '90.1-2013', 'NECB2011' model.getWaterHeaterMixeds.sort.each do |water_heater| water_heater.setOffCycleLossCoefficienttoAmbientTemperature(7.561562668) water_heater.setOnCycleLossCoefficienttoAmbientTemperature(7.561562668) end end end |