A variety of fan calculation methods that are the same regardless of fan type. These methods are available to FanConstantVolume, FanOnOff, FanVariableVolume, and FanZoneExhaust
Fan collapse
-
#fan_adjust_pressure_rise_to_meet_fan_power(fan, target_fan_power) ⇒ Boolean
Adjust the fan pressure rise to hit the target fan power (W).
-
#fan_apply_standard_minimum_motor_efficiency(fan, allowed_bhp) ⇒ Boolean
Applies the minimum motor efficiency for this fan based on the motor’s brake horsepower.
-
#fan_baseline_impeller_efficiency(fan) ⇒ Double
Determines the baseline fan impeller efficiency based on the specified fan type.
-
#fan_brake_horsepower(fan) ⇒ Double
Determines the brake horsepower of the fan based on fan power and fan motor efficiency.
-
#fan_change_impeller_efficiency(fan, impeller_eff) ⇒ Boolean
Changes the fan impeller efficiency and also the fan total efficiency at the same time, preserving the motor efficiency.
-
#fan_change_motor_efficiency(fan, motor_eff) ⇒ Boolean
Changes the fan motor efficiency and also the fan total efficiency at the same time, preserving the impeller efficiency.
-
#fan_design_air_flow(fan) ⇒ Double
Determines the design fan flow (m3/s).
-
#fan_fanpower(fan) ⇒ Double
Determines the fan power (W) based on flow rate, pressure rise, and total fan efficiency(impeller eff * motor eff).
-
#fan_motor_horsepower(fan) ⇒ Double
Determines the horsepower of the fan motor, including motor efficiency and fan impeller efficiency.
-
#fan_rated_w_per_cfm(fan) ⇒ Double
Find the actual rated fan power per flow (W/CFM) by querying the sql file.
-
#fan_small_fan?(fan) ⇒ Boolean
Zone exhaust fans, fan coil unit fans, and powered VAV terminal fans all count as small fans and get different impeller efficiencies and motor efficiencies than other fans.
-
#fan_standard_minimum_motor_efficiency_and_size(fan, motor_bhp) ⇒ Array<Double>
Determines the minimum fan motor efficiency and nominal size for a given motor bhp.
Instance Method Details
#fan_adjust_pressure_rise_to_meet_fan_power(fan, target_fan_power) ⇒ Boolean
Adjust the fan pressure rise to hit the target fan power (W). Keep the fan impeller and motor efficiencies static.
43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 43 def fan_adjust_pressure_rise_to_meet_fan_power(fan, target_fan_power) # Get design supply air flow rate (whether autosized or hard-sized) dsn_air_flow_m3_per_s = 0 dsn_air_flow_m3_per_s = if fan.maximumFlowRate.is_initialized fan.maximumFlowRate.get elsif fan.autosizedMaximumFlowRate.is_initialized fan.autosizedMaximumFlowRate.get end # Get the current fan power current_fan_power_w = fan_fanpower(fan) # Get the current pressure rise (Pa) pressure_rise_pa = fan.pressureRise # Get the total fan efficiency fan_total_eff = fan.fanEfficiency # Calculate the new fan pressure rise (Pa) new_pressure_rise_pa = target_fan_power * fan_total_eff / dsn_air_flow_m3_per_s new_pressure_rise_in_h2o = OpenStudio.convert(new_pressure_rise_pa, 'Pa', 'inH_{2}O').get # Set the new pressure rise fan.setPressureRise(new_pressure_rise_pa) # Calculate the new power new_power_w = fan_fanpower(fan) OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.Fan', "For #{fan.name}: pressure rise = #{new_pressure_rise_in_h2o.round(1)} in w.c., power = #{fan_motor_horsepower(fan).round(2)}HP.") return true end |
#fan_apply_standard_minimum_motor_efficiency(fan, allowed_bhp) ⇒ Boolean
Applies the minimum motor efficiency for this fan based on the motor’s brake horsepower.
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 12 def fan_apply_standard_minimum_motor_efficiency(fan, allowed_bhp) # Find the motor efficiency motor_eff, nominal_hp = fan_standard_minimum_motor_efficiency_and_size(fan, allowed_bhp) # Change the motor efficiency # but preserve the existing fan impeller # efficiency. fan_change_motor_efficiency(fan, motor_eff) # Calculate the total motor HP motor_hp = fan_motor_horsepower(fan) # Exception for small fans, including # zone exhaust, fan coil, and fan powered terminals. # In this case, 0.5 HP is used for the lookup. if fan_small_fan?(fan) OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.Fan', "For #{fan.name}: motor eff = #{(motor_eff * 100).round(2)}%; assumed to represent several less than 1 HP motors.") else OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.Fan', "For #{fan.name}: motor nameplate = #{nominal_hp}HP, motor eff = #{(motor_eff * 100).round(2)}%.") end return true end |
#fan_baseline_impeller_efficiency(fan) ⇒ Double
Add fan type to data model and modify this method
Determines the baseline fan impeller efficiency based on the specified fan type.
215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 215 def fan_baseline_impeller_efficiency(fan) # Assume that the fan efficiency is 65% for normal fans # and 55% for small fans (like exhaust fans). # @todo add fan type to fan data model # and infer impeller efficiency from that? # or do we always assume a certain type of # fan impeller for the baseline system? # @todo check COMNET and T24 ACM and PNNL 90.1 doc fan_impeller_eff = 0.65 if fan_small_fan?(fan) fan_impeller_eff = 0.55 end return fan_impeller_eff end |
#fan_brake_horsepower(fan) ⇒ Double
Determines the brake horsepower of the fan based on fan power and fan motor efficiency.
127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 127 def fan_brake_horsepower(fan) # Get the fan motor efficiency existing_motor_eff = 0.7 if fan.to_FanZoneExhaust.empty? existing_motor_eff = fan.motorEfficiency end # Get the fan power (W) fan_power_w = fan_fanpower(fan) # Calculate the brake horsepower (bhp) fan_bhp = fan_power_w * existing_motor_eff / 746 return fan_bhp end |
#fan_change_impeller_efficiency(fan, impeller_eff) ⇒ Boolean
Changes the fan impeller efficiency and also the fan total efficiency at the same time, preserving the motor efficiency.
194 195 196 197 198 199 200 201 202 203 204 205 206 207 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 194 def fan_change_impeller_efficiency(fan, impeller_eff) # Get the existing motor efficiency existing_motor_eff = 0.7 if fan.to_FanZoneExhaust.empty? existing_motor_eff = fan.motorEfficiency end # Calculate the new total efficiency new_total_eff = existing_motor_eff * impeller_eff # Set the revised motor and total fan efficiencies fan.setFanEfficiency(new_total_eff) return true end |
#fan_change_motor_efficiency(fan, motor_eff) ⇒ Boolean
Changes the fan motor efficiency and also the fan total efficiency at the same time, preserving the impeller efficiency.
165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 165 def fan_change_motor_efficiency(fan, motor_eff) # Calculate the existing impeller efficiency existing_motor_eff = 0.7 if fan.to_FanZoneExhaust.empty? existing_motor_eff = fan.motorEfficiency end existing_total_eff = fan.fanEfficiency existing_impeller_eff = existing_total_eff / existing_motor_eff # Calculate the new total efficiency new_total_eff = motor_eff * existing_impeller_eff # Set the revised motor and total fan efficiencies if fan.to_FanZoneExhaust.is_initialized fan.setFanEfficiency(new_total_eff) else fan.setFanEfficiency(new_total_eff) fan.setMotorEfficiency(motor_eff) end return true end |
#fan_design_air_flow(fan) ⇒ Double
Determines the design fan flow (m3/s)
81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 81 def fan_design_air_flow(fan) # Get design supply air flow rate (whether autosized or hard-sized) dsn_air_flow_m3_per_s = if fan.to_FanZoneExhaust.empty? if fan.maximumFlowRate.is_initialized fan.maximumFlowRate.get elsif fan.autosizedMaximumFlowRate.is_initialized fan.autosizedMaximumFlowRate.get else OpenStudio.logFree(OpenStudio::Error, 'openstudio.standards.Fan', "The maximum flow rate for fan '#{fan.name}' was neither specified nor set to Autosize.") end else if fan.maximumFlowRate.is_initialized fan.maximumFlowRate.get else OpenStudio.logFree(OpenStudio::Error, 'openstudio.standards.Fan', "The maximum flow rate for exhaust fan '#{fan.name}' was not specified.") end end return dsn_air_flow_m3_per_s end |
#fan_fanpower(fan) ⇒ Double
Determines the fan power (W) based on flow rate, pressure rise, and total fan efficiency(impeller eff * motor eff)
107 108 109 110 111 112 113 114 115 116 117 118 119 120 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 107 def fan_fanpower(fan) # Get the total fan efficiency, # which in E+ includes both motor and # impeller efficiency. fan_total_eff = fan.fanEfficiency # Get the pressure rise (Pa) pressure_rise_pa = fan.pressureRise # Calculate the fan power (W) fan_power_w = pressure_rise_pa * fan_design_air_flow(fan) / fan_total_eff return fan_power_w end |
#fan_motor_horsepower(fan) ⇒ Double
Determines the horsepower of the fan motor, including motor efficiency and fan impeller efficiency.
148 149 150 151 152 153 154 155 156 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 148 def fan_motor_horsepower(fan) # Get the fan power fan_power_w = fan_fanpower(fan) # Convert to HP fan_hp = fan_power_w / 745.7 # 745.7 W/HP return fan_hp end |
#fan_rated_w_per_cfm(fan) ⇒ Double
Find the actual rated fan power per flow (W/CFM) by querying the sql file
341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 341 def fan_rated_w_per_cfm(fan) # Get design power (whether autosized or hard-sized) rated_power_w = fan_fanpower(fan) if fan.maximumFlowRate.is_initialized max_m3_per_s = fan.ratedFlowRate.get elsif fan.autosizedMaximumFlowRate.is_initialized max_m3_per_s = fan.autosizedMaximumFlowRate.get else OpenStudio.logFree(OpenStudio::Error, 'openstudio.standards.Fan', "For #{fan.name}, could not find fan Maximum Flow Rate, cannot determine w per cfm correctly.") return false end rated_w_per_m3s = rated_power_w / max_m3_per_s rated_w_per_cfm = OpenStudio.convert(rated_w_per_m3s, 'W*s/m^3', 'W*min/ft^3').get return rated_w_per_cfm end |
#fan_small_fan?(fan) ⇒ Boolean
Zone exhaust fans, fan coil unit fans, and powered VAV terminal fans all count as small fans and get different impeller efficiencies and motor efficiencies than other fans
309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 309 def fan_small_fan?(fan) is_small = false # Exhaust fan if fan.to_FanZoneExhaust.is_initialized is_small = true # Fan coil unit, unit heater, PTAC, PTHP, VRF terminals, WSHP, ERV elsif fan.containingZoneHVACComponent.is_initialized zone_hvac = fan.containingZoneHVACComponent.get if zone_hvac.to_ZoneHVACFourPipeFanCoil.is_initialized is_small = true # elsif zone_hvac.to_ZoneHVACUnitHeater.is_initialized # is_small = true elsif zone_hvac.to_ZoneHVACPackagedTerminalAirConditioner.is_initialized || zone_hvac.to_ZoneHVACPackagedTerminalHeatPump.is_initialized || zone_hvac.to_ZoneHVACTerminalUnitVariableRefrigerantFlow.is_initialized || zone_hvac.to_ZoneHVACWaterToAirHeatPump.is_initialized || zone_hvac.to_ZoneHVACEnergyRecoveryVentilator.is_initialized is_small = true end # Powered VAV terminal elsif fan.containingHVACComponent.is_initialized zone_hvac = fan.containingHVACComponent.get if zone_hvac.to_AirTerminalSingleDuctParallelPIUReheat.is_initialized || zone_hvac.to_AirTerminalSingleDuctSeriesPIUReheat.is_initialized is_small = true end end return is_small end |
#fan_standard_minimum_motor_efficiency_and_size(fan, motor_bhp) ⇒ Array<Double>
Determines the minimum fan motor efficiency and nominal size for a given motor bhp. This should be the total brake horsepower with any desired safety factor already included. This method picks the next nominal motor catgory larger than the required brake horsepower, and the efficiency is based on that size. For example, if the bhp = 6.3, the nominal size will be 7.5HP and the efficiency for 90.1-2010 will be 91.7% from Table 10.8B. This method assumes 4-pole, 1800rpm totally-enclosed fan-cooled motors.
244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 |
# File 'lib/openstudio-standards/standards/Standards.Fan.rb', line 244 def fan_standard_minimum_motor_efficiency_and_size(fan, motor_bhp) fan_motor_eff = 0.85 nominal_hp = motor_bhp # Don't attempt to look up motor efficiency # for zero-hp fans, which may occur when there is no # airflow required for a particular system, typically # heated-only spaces with high internal gains # and no OA requirements such as elevator shafts. return [fan_motor_eff, 0] if motor_bhp < 0.0001 # Lookup the minimum motor efficiency motors = standards_data['motors'] # Assuming all fan motors are 4-pole ODP search_criteria = { 'template' => template, 'number_of_poles' => 4.0, 'type' => 'Enclosed' } # Exception for small fans, including # zone exhaust, fan coil, and fan powered terminals. # In this case, use the 0.5 HP for the lookup. if fan_small_fan?(fan) nominal_hp = 0.5 else motor_properties = model_find_object(motors, search_criteria, motor_bhp) if motor_properties.nil? OpenStudio.logFree(OpenStudio::Error, 'openstudio.standards.Fan', "For #{fan.name}, could not find motor properties using search criteria: #{search_criteria}, motor_bhp = #{motor_bhp} hp.") return [fan_motor_eff, nominal_hp] end nominal_hp = motor_properties['maximum_capacity'].to_f.round(1) # If the biggest fan motor size is hit, use the highest category efficiency if nominal_hp > 9998.0 OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.Fan', "For #{fan.name}, there is no greater nominal HP. Use the efficiency of the largest motor category.") nominal_hp = motor_bhp end # Round to nearest whole HP for niceness if nominal_hp >= 2 nominal_hp = nominal_hp.round end end # Get the efficiency based on the nominal horsepower # Add 0.01 hp to avoid search errors. motor_properties = model_find_object(motors, search_criteria, nominal_hp + 0.01) if motor_properties.nil? OpenStudio.logFree(OpenStudio::Error, 'openstudio.standards.Fan', "For #{fan.name}, could not find nominal motor properties using search criteria: #{search_criteria}, motor_hp = #{nominal_hp} hp.") return [fan_motor_eff, nominal_hp] end fan_motor_eff = motor_properties['nominal_full_load_efficiency'] return [fan_motor_eff, nominal_hp] end |